Kbox LGE - LG BYR Port KNX Gateway

Kbox LGE - LG BYR Port KNX Gateway

Kbox LGE - LG BYR Port KNX Gateway — KNX gateway

Product Features

Kbox LGE connects LG air conditioners to a KNX automation system. The link is made through the indoor unit's BYR controller port: the gateway drives the unit from KNX and reports its state back to the bus.

The standout feature of Kbox LGE is its Slave Function: the device can run in parallel with an existing wired remote controller. The user keeps using the controller on the wall while the air conditioner is also controlled from KNX — the controller does not have to be removed or disabled. That makes KNX retrofits in existing buildings noticeably simpler.

The setpoint can be limited to 18–30 °C in both cooling and heating. Fan runs as 4 levels plus Auto.

Integration Notes

  • Vane control is not position based: Kbox LGE has no addressable positions for the vertical vane; the vane is driven only by a 1-bit Swing on/off object. If you are planning a visualisation that places the vane at discrete angles, do not expect the behaviour of a model that does expose positions, such as Kbox MDA with its 7 positions. The horizontal vane (Left-Right Wing) is supported.
  • Ambient temperature: the ambient temperature is fed over the KNX bus. Passing a KNX room thermostat's reading to the air conditioner gives a more stable comfort temperature than the indoor unit's suction sensor.
  • Controller lock: the "Remote Controller Lock" object blocks commands from the wired controller; control from the KNX side is unaffected.

Documents & Downloads

Catalog English

Datasheet

User Manual

ETS Database

Box Contents

  • Kbox-LGE KNX gateway
  • Wago KNX Terminal

Technical Specifications

DeviceKbox LGE - LG BYR Port KNX Gateway
AC brandLG
Connection portBYR
Compatible indoor unitsLG indoor units
ETS application version1.0.8
KNX certificate no.574/22153/25 (KNX v3.0.4)
Power supplyKNX bus (EIB)
Power consumption10 mA
Inputs3 dry contact inputs
Button / LED1 × KNX programming button · 1 × KNX programming LED
Operating modeS-Mode
Protection classIP20
Working temperature-10 °C … +70 °C
Storage temperature-25 °C … +90 °C
Max. humidity< 90 % RH
Dimensions44.5 × 19.8 × 44.5 mm
ConfigurationETS 5 / ETS 6

ETS Parameters

The device connects to the LG indoor unit through the BYR port. The parameters below are configured in ETS.

Operating modesCool / Heat / Dry / Fan Only / Auto
Fan speed4 levels + Auto
Up-Down WingSwing on/off only
Left-Right WingYes
Cooling setpoint range18 – 30 °C
Heating setpoint range18 – 30 °C
Ambient temperature sourceFrom the KNX bus (From Bus)
Slave Function (parallel with a wired remote controller)Yes

KNX Group Objects

The device exposes 46 group objects. Object names are given exactly as they appear in the ETS database.

ObjectFunctionTypeFlags
General
On/Off1: On / 0: Off1 bitCWU
On/Off Feedback1: On / 0: Off1 bitCRT
Alive StatusAlive notification1 bitCRT
Remote Controller Lock1: Enabled / 0: Disabled1 bitCRWU
Object Control Lock1: Enabled / 0: Disabled1 bitCRWU
Error StatusASCII error code14 bytesCRT
Error Alarm1: On / 0: Off1 byteCRT
Mode
ModeCool / Heat / Dry (Dehumidification) / Fan (Fan Only) / Auto1 byteCWU
Mode FeedbackCool / Heat / Dry (Dehumidification) / Fan (Fan Only) / Auto1 byteCRT
Mode +/-1: Increase / 0: Decrease1 bitCWU
Heat/Cool Mode Set1: Heat / 0: Cool1 bitCWU
Cool Mode Set1: Enable / 0: Disable1 bitCWU
Heat Mode Set1: Enable / 0: Disable1 bitCWU
Dry (Dehumidification) Mode Set1: Enable / 0: Disable1 bitCWU
Fan (Fan Only) Mode Set1: Enable / 0: Disable1 bitCWU
Auto Mode Set1: Enable / 0: Disable1 bitCWU
Cool Mode Feedback1: Enable / 0: Disable1 bitCRT
Heat Mode Feedback1: Enable / 0: Disable1 bitCRT
Dry (Dehumidification) Mode Feedback1: Enable / 0: Disable1 bitCRT
Fan (Fan Only) Mode Feedback1: Enable / 0: Disable1 bitCRT
Auto Mode Feedback1: Enable / 0: Disable1 bitCRT
Temperature
Set Point TemperatureTemperature (°C)2 bytesCWU
Set Point Temperature FeedbackTemperature (°C)2 bytesCRT
Set Point Temperature +/-1: Increase / 0: Decrease1 bitCWU
Ambient TemperatureTemperature (°C), min 8 / max 392 bytesCWU
Ambient Temperature FeedbackTemperature (°C)2 bytesCRT
Fan
Fan Level SetPercentage (Scaling)1 byteCWU
Fan Level FeedbackPercentage (Scaling)1 byteCRT
Fan Level Set0…4 (Enumerated)1 byteCWU
Fan Level Feedback0…4 (Enumerated)1 byteCRT
Fan Level +/- Set1: Increase / 0: Decrease1 bitCWU
Fan Level-1 Set1: Enable / 0: Disable1 bitCWU
Fan Level-2 Set1: Enable / 0: Disable1 bitCWU
Fan Level-3 Set1: Enable / 0: Disable1 bitCWU
Fan Level-4 Set1: Enable / 0: Disable1 bitCWU
Fan Level-1 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-2 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-3 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-4 Feedback1: Enable / 0: Disable1 bitCRT
Up-Down Wing
Up-Down Position Swing Set1: Enabled / 0: Disabled1 bitCWU
Up-Down Position Swing Feedback1: Enabled / 0: Disabled1 bitCRT
Left-Right Wing
Left-Right Position Swing Set1: Enabled / 0: Disabled1 bitCWU
Left-Right Position Swing Feedback1: Enabled / 0: Disabled1 bitCRT
Digital Inputs
Digital Input 11: Active / 0: Passive1 bitCWU
Digital Input 21: Active / 0: Passive1 bitCWU
Digital Input 31: Active / 0: Passive1 bitCWU

Flags: C = Communication, R = Read, W = Write, T = Transmit, U = Update.