Kbox MHVY - Mitsubishi Heavy XY KNX Gateway

Kbox MHVY - Mitsubishi Heavy XY KNX Gateway

Kbox MHVY - Mitsubishi Heavy XY KNX Gateway — KNX gateway

Product Features

Kbox MHVY connects Mitsubishi Heavy Industries air conditioners to a KNX automation system. The link is made over the indoor unit's X/Y communication line.

This is the only device in the Kbox family that makes the ambient temperature source selectable. The "Ambient Temperature Source" parameter in ETS either feeds the temperature from the KNX bus (From Bus) or reads it from the air conditioner's suction air sensor and reports it back to KNX (From AC). The second option carries temperature data onto the bus without the cost of a separate sensor in projects that have no KNX temperature sensor in the room.

The device can run in parallel with an existing wired controller through its Slave Function. The setpoint is limited to 18–30 °C in cooling and 16–30 °C in heating.

Integration Notes

  • There is no Fan Auto: on Kbox MHVY the fan runs as 4 fixed levels; an Auto step does not exist. Account for that if you are planning an "Auto" option for the fan in a visualisation or BMS.
  • There is no horizontal vane: the device controls only the vertical vane (Up-Down Wing, 4 positions plus Swing). Left-Right Wing is not supported — reflect that in the design on projects that need horizontal vane control.
  • When From AC is selected: only the "Ambient Temperature Feedback" group object remains visible; the "Ambient Temperature" object used to write the temperature from the bus disappears. Any visualisation bound to the write object has to be reviewed alongside this choice.
  • Compatibility: verify your indoor unit model in the compatibility finder.

Documents & Downloads

Catalog Turkish

Catalog English

Datasheet

User Manual

ETS Database

Box Contents

  • Kbox-MHVY KNX gateway
  • Wago KNX Terminal

Technical Specifications

DeviceKbox MHVY - Mitsubishi Heavy XY KNX Gateway
AC brandMitsubishi Heavy
Connection portX/Y
Compatible indoor unitsMitsubishi Heavy indoor units
ETS application version1.0.8
KNX certificate no.574/22153/25 (KNX v3.0.4)
Power supplyKNX bus (EIB)
Power consumption10 mA
Inputs3 dry contact inputs
Button / LED1 × KNX programming button · 1 × KNX programming LED
Operating modeS-Mode
Protection classIP20
Working temperature-10 °C … +70 °C
Storage temperature-25 °C … +90 °C
Max. humidity< 90 % RH
Dimensions44.5 × 19.8 × 44.5 mm
ConfigurationETS 5 / ETS 6

ETS Parameters

The device connects to the Mitsubishi Heavy indoor unit through the X/Y port. The parameters below are configured in ETS.

Operating modesCool / Heat / Dry / Fan Only / Auto
Fan speed4 levels (no Auto)
Up-Down Wing4 addressable positions + Swing
Left-Right WingNo
Cooling setpoint range18 – 30 °C
Heating setpoint range16 – 30 °C
Ambient temperature sourceSelectable: From Bus / From AC
Slave Function (parallel with a wired remote controller)Yes

KNX Group Objects

The device exposes 55 group objects. Object names are given exactly as they appear in the ETS database.

ObjectFunctionTypeFlags
General
On/Off1: On / 0: Off1 bitCWU
On/Off Feedback1: On / 0: Off1 bitCRT
Alive StatusAlive notification1 bitCRT
Remote Controller Lock1: Enabled / 0: Disabled1 bitCRWU
Object Control Lock1: Enabled / 0: Disabled1 bitCRWU
Error StatusASCII error code14 bytesCRT
Error Alarm1: On / 0: Off1 byteCRT
Mode
ModeCool / Heat / Dry (Dehumidification) / Fan (Fan Only) / Auto1 byteCWU
Mode FeedbackCool / Heat / Dry (Dehumidification) / Fan (Fan Only) / Auto1 byteCRT
Mode +/-1: Increase / 0: Decrease1 bitCWU
Heat/Cool Mode Set1: Heat / 0: Cool1 bitCWU
Cool Mode Set1: Enable / 0: Disable1 bitCWU
Heat Mode Set1: Enable / 0: Disable1 bitCWU
Dry (Dehumidification) Mode Set1: Enable / 0: Disable1 bitCWU
Fan (Fan Only) Mode Set1: Enable / 0: Disable1 bitCWU
Auto Mode Set1: Enable / 0: Disable1 bitCWU
Cool Mode Feedback1: Enable / 0: Disable1 bitCRT
Heat Mode Feedback1: Enable / 0: Disable1 bitCRT
Dry (Dehumidification) Mode Feedback1: Enable / 0: Disable1 bitCRT
Fan (Fan Only) Mode Feedback1: Enable / 0: Disable1 bitCRT
Auto Mode Feedback1: Enable / 0: Disable1 bitCRT
Temperature
Set Point TemperatureTemperature (°C)2 bytesCWU
Set Point Temperature FeedbackTemperature (°C)2 bytesCRT
Set Point Temperature +/-1: Increase / 0: Decrease1 bitCWU
Ambient TemperatureTemperature (°C), min 8 / max 392 bytesCWU
Ambient Temperature FeedbackTemperature (°C)2 bytesCRT
Fan
Fan Level SetPercentage (Scaling)1 byteCWU
Fan Level FeedbackPercentage (Scaling)1 byteCRT
Fan Level Set1…4 (Enumerated)1 byteCWU
Fan Level Feedback1…4 (Enumerated)1 byteCRT
Fan Level +/- Set1: Increase / 0: Decrease1 bitCWU
Fan Level-1 Set1: Enable / 0: Disable1 bitCWU
Fan Level-2 Set1: Enable / 0: Disable1 bitCWU
Fan Level-3 Set1: Enable / 0: Disable1 bitCWU
Fan Level-4 Set1: Enable / 0: Disable1 bitCWU
Fan Level-1 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-2 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-3 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-4 Feedback1: Enable / 0: Disable1 bitCRT
Up-Down Wing
Up-Down Wing SetPercentage (Scaling)1 byteCWU
Up-Down Wing FeedbackPercentage (Scaling)1 byteCRT
Up-Down Wing Set1…4 (Enumerated)1 byteCWU
Up-Down Wing Feedback1…4 (Enumerated)1 byteCRT
Up-Down Wing +/- Set1: Increase / 0: Decrease1 bitCWU
Up-Down Wing Position 1 Set1: Set Position 1 / 0: NA1 bitCWU
Up-Down Wing Position 2 Set1: Set Position 2 / 0: NA1 bitCWU
Up-Down Wing Position 3 Set1: Set Position 3 / 0: NA1 bitCWU
Up-Down Wing Position 4 Set1: Set Position 4 / 0: NA1 bitCWU
Up-Down Wing Position 1 Feedback1: Active / 0: Inactive1 bitCRT
Up-Down Wing Position 2 Feedback1: Active / 0: Inactive1 bitCRT
Up-Down Wing Position 3 Feedback1: Active / 0: Inactive1 bitCRT
Up-Down Wing Position 4 Feedback1: Active / 0: Inactive1 bitCRT
Digital Inputs
Digital Input 11: Active / 0: Passive1 bitCWU
Digital Input 21: Active / 0: Passive1 bitCWU
Digital Input 31: Active / 0: Passive1 bitCWU

Flags: C = Communication, R = Read, W = Write, T = Transmit, U = Update.