Kbox DKN-M-S21 - Daikin Multi S21 KNX Gateway

Kbox DKN-M-S21 - Daikin Multi S21 KNX Gateway

Kbox DKN-M-S21 - Daikin Multi S21 KNX Gateway — KNX gateway

Product Features

Kbox DKN-M-S21 connects Daikin indoor units to a KNX automation system through the S21 port. S21 is the service connector found on Daikin's residential and multi-split indoor units.

This model stretches the limits of the Kbox family in two places. First, fan control is addressed as 7 levels plus Auto — the highest step count in the family. Second, the heating setpoint can be taken down to 10 °C (10–30 °C), the lowest floor in the family and the basis for frost-protection scenarios in unoccupied spaces. In cooling the range is 18–32 °C.

Integration Notes

  • Do not confuse it with VRV: the S21 port is for residential and multi-split units. Daikin VRV systems use the P1/P2 line and need the Kbox DKN model. The two are not interchangeable.
  • There is no Slave Function: this model does not support running in parallel with a wired remote controller. Evaluate that at design stage on a project where the existing controller has to stay in place.
  • Vane control is not position based: the vertical vane is driven only by a 1-bit Swing on/off object; there are no addressable positions. The horizontal vane (Left-Right Wing) is supported.
  • Frost protection: a 10 °C heating floor, combined with a window contact or occupancy sensor on the KNX side, keeps unused rooms at a low temperature.
  • Compatibility: verify your indoor unit model in the compatibility finder.

Documents & Downloads

Catalog

Datasheet

User Manual

ETS Database

Box Contents

  • Kbox-DKN-M-S21 KNX gateway
  • S21 Connection Cable
  • Wago KNX Terminal

Technical Specifications

DeviceKbox DKN-M-S21 - Daikin Multi S21 KNX Gateway
AC brandDaikin
Connection portS21
Compatible indoor unitsDaikin indoor units
ETS application version1.0.8
KNX certificate no.574/22153/25 (KNX v3.0.4)
Power supplyKNX bus (EIB)
Power consumption10 mA
Inputs3 dry contact inputs
Button / LED1 × KNX programming button · 1 × KNX programming LED
Operating modeS-Mode
Protection classIP20
Working temperature-10 °C … +70 °C
Storage temperature-25 °C … +90 °C
Max. humidity< 90 % RH
Dimensions44.5 × 19.8 × 44.5 mm
ConfigurationETS 5 / ETS 6

ETS Parameters

The device connects to the Daikin indoor unit through the S21 port. The parameters below are configured in ETS.

Operating modesCool / Heat / Dry / Fan Only / Auto
Fan speed7 levels + Auto
Up-Down WingSwing on/off only
Left-Right WingYes
Cooling setpoint range18 – 32 °C
Heating setpoint range10 – 30 °C
Ambient temperature sourceFrom the KNX bus (From Bus)

KNX Group Objects

The device exposes 52 group objects. Object names are given exactly as they appear in the ETS database.

ObjectFunctionTypeFlags
General
On/Off1: On / 0: Off1 bitCWU
On/Off Feedback1: On / 0: Off1 bitCRT
Alive StatusAlive notification1 bitCRT
Remote Controller Lock1: Enabled / 0: Disabled1 bitCRWU
Object Control Lock1: Enabled / 0: Disabled1 bitCRWU
Error StatusASCII error code14 bytesCRT
Error Alarm1: On / 0: Off1 byteCRT
Mode
ModeCool / Heat / Dry (Dehumidification) / Fan (Fan Only) / Auto1 byteCWU
Mode FeedbackCool / Heat / Dry (Dehumidification) / Fan (Fan Only) / Auto1 byteCRT
Mode +/-1: Increase / 0: Decrease1 bitCWU
Heat/Cool Mode Set1: Heat / 0: Cool1 bitCWU
Cool Mode Set1: Enable / 0: Disable1 bitCWU
Heat Mode Set1: Enable / 0: Disable1 bitCWU
Dry (Dehumidification) Mode Set1: Enable / 0: Disable1 bitCWU
Fan (Fan Only) Mode Set1: Enable / 0: Disable1 bitCWU
Auto Mode Set1: Enable / 0: Disable1 bitCWU
Cool Mode Feedback1: Enable / 0: Disable1 bitCRT
Heat Mode Feedback1: Enable / 0: Disable1 bitCRT
Dry (Dehumidification) Mode Feedback1: Enable / 0: Disable1 bitCRT
Fan (Fan Only) Mode Feedback1: Enable / 0: Disable1 bitCRT
Auto Mode Feedback1: Enable / 0: Disable1 bitCRT
Temperature
Set Point TemperatureTemperature (°C)2 bytesCWU
Set Point Temperature FeedbackTemperature (°C)2 bytesCRT
Set Point Temperature +/-1: Increase / 0: Decrease1 bitCWU
Ambient TemperatureTemperature (°C), min 8 / max 392 bytesCWU
Ambient Temperature FeedbackTemperature (°C)2 bytesCRT
Fan
Fan Level SetPercentage (Scaling)1 byteCWU
Fan Level FeedbackPercentage (Scaling)1 byteCRT
Fan Level Set0…7 (Enumerated)1 byteCWU
Fan Level Feedback0…7 (Enumerated)1 byteCRT
Fan Level +/- Set1: Increase / 0: Decrease1 bitCWU
Fan Level-1 Set1: Enable / 0: Disable1 bitCWU
Fan Level-2 Set1: Enable / 0: Disable1 bitCWU
Fan Level-3 Set1: Enable / 0: Disable1 bitCWU
Fan Level-4 Set1: Enable / 0: Disable1 bitCWU
Fan Level-5 Set1: Enable / 0: Disable1 bitCWU
Fan Level-6 Set1: Enable / 0: Disable1 bitCWU
Fan Level-7 Set1: Enable / 0: Disable1 bitCWU
Fan Level-1 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-2 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-3 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-4 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-5 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-6 Feedback1: Enable / 0: Disable1 bitCRT
Fan Level-7 Feedback1: Enable / 0: Disable1 bitCRT
Up-Down Wing
Up-Down Position Swing Set1: Enabled / 0: Disabled1 bitCWU
Up-Down Position Swing Feedback1: Enabled / 0: Disabled1 bitCRT
Left-Right Wing
Left-Right Position Swing Set1: Enabled / 0: Disabled1 bitCWU
Left-Right Position Swing Feedback1: Enabled / 0: Disabled1 bitCRT
Digital Inputs
Digital Input 11: Active / 0: Passive1 bitCWU
Digital Input 21: Active / 0: Passive1 bitCWU
Digital Input 31: Active / 0: Passive1 bitCWU

Flags: C = Communication, R = Read, W = Write, T = Transmit, U = Update.